Browser screen size: *
OCC-PIR/RAD-2
Occupancy Sensor w/Multi-Tech. PIR & Radar
Overview
The OCC-PIR/RAD-2 occupancy sensor is directly connected to the ELC communication line and performs relay ON/OFF control or dimming control for lighting fixtures according to occupancy detection.
This occupancy sensor combines infrared thermal detection and radar sensing technology, providing dual sensing capability through multi-technology detection.
This design minimizes unintended shut-off situations and enables stable and continuous occupancy-based control.
This occupancy sensor combines infrared thermal detection and radar sensing technology, providing dual sensing capability through multi-technology detection.
This design minimizes unintended shut-off situations and enables stable and continuous occupancy-based control.
Feature
- Compact sensor design
- Maximum detection area: 92.9m², 360° coverage
- Built-in time delay and sensitivity adjustment switches
- Compact ceiling-mounted structure
- Infrared and radar sensing technology
- Maximum detection distance: 14 meters
- Built-in operation delay and detection range adjustment switches
- Compact ceiling-mount installation with simple mounting method
- Integrated sensor communication module for direct connection to ELC systems via 4-wire communication/power line
- Occupancy sensing mode: Select “0” when connected to ELC systems. Select levels 1–15 for sensitivity adjustment and dry contact output when connected to third-party systems.
- Smart sensing function: Detects and filters frequent human movement for more accurate occupancy sensing.
Operation
Application
In ELC systems, this sensor is connected through the communication line, and the sensitivity selector should be set to “0”.
When connected to third-party systems, sensitivity levels from 1 to 15 can be selected, allowing both sensitivity adjustment and dry contact signal output.
The sensor combines infrared thermal sensing and radar sensing technologies to minimize unwanted shut-off conditions and provide highly reliable occupancy sensing performance.
When connected to third-party systems, sensitivity levels from 1 to 15 can be selected, allowing both sensitivity adjustment and dry contact signal output.
The sensor combines infrared thermal sensing and radar sensing technologies to minimize unwanted shut-off conditions and provide highly reliable occupancy sensing performance.
Specification
- Passive infrared and radar sensing
- Mounting: Ceiling
- Detection distance: 14 meters
- Detection pattern: 360°
- Adjustment: Self-adjustment
- Isolated relay: Yes
- Manual time adjustment: 5 seconds – 30 minutes, 16-step selection mode
- Sensitivity setting: 0 = ELC system communication mode, 1–15 = sensitivity adjustment and dry contact signal output
- Smart sensing function supported
- Input voltage: 24VDC
- Current consumption: 100mA
- Operating conditions: 0 - 50ºC, 0 - 95% RH
- Certification: KC
Network
Dimension
User Interface
Layout
System Diagram
Connect Diagram