Application

Enhancing Building Value Through Optimized Solutions

화면 로딩 중...
Energy Saving Analysis
On/Off System
On/Off System Energy Saving Analysis
On/Off System Energy Saving Plan
  • Apply schedule-based control considering commuting and lunch hours. Control lighting throughout the entire area at 50% and 25% during start-of-work and lunch periods.
  • Window-side control targets 10W DOWN LIGHTs in the perimeter area. When the illuminance sensor installed near the windows detects 500 LUX, the window-side lighting is controlled at 50%. When the illuminance does not reach 550 LUX, the remaining window-side lighting is controlled at 0%.
  • Install occupancy sensors and window-side illuminance sensors in patient rooms, meeting rooms, lounges, and similar areas. Window-side lighting is controlled in the same manner as office areas, while the remaining areas are controlled at 0% when vacancy is detected by the occupancy sensor.
0-10V Dimming System
0-10V Dimming System Energy Saving Analysis
0-10V Dimming System Energy Saving Plan
  • Apply schedule-based control considering commuting and lunch hours. Control lighting throughout the entire area at 50% and 25% during start-of-work and lunch periods using dimming control.
  • Window-side control targets 10W DOWN LIGHTs in the perimeter area. When the illuminance sensor installed near the windows detects 500 LUX, control the window-side LED lighting by dimming from 70% to 30%. When 550 LUX is detected, control the remaining window-side lighting at 0% dimming.
  • Install occupancy sensors and window-side illuminance sensors in executive offices, meeting rooms, lounges, and similar areas. Window-side lighting is controlled in the same manner as office areas, while the remaining areas use step-by-step dimming control (70%, 30%, 0%) when vacancy is detected by the occupancy sensor.
DALI + Dimming System
DALI + Dimming System Energy Saving Analysis
DALI + Dimming System Energy Saving Plan
  • Apply schedule-based control considering commuting and lunch hours. Control lighting throughout the entire area at 50% and 25% during start-of-work and lunch periods using dimming control.
  • Window-side control targets 10W DOWN LIGHTs in the perimeter area. When the illuminance sensor installed near the windows detects 500 LUX, control the window-side LED lighting by dimming from 70% to 30%. When 550 LUX is detected, control the remaining window-side lighting at 0% dimming. In addition, the first row of 25W LEDs near the office windows is also controlled by setting the dimming level from 70% to 30%.
  • Install occupancy sensors and window-side illuminance sensors in executive offices, meeting rooms, lounges, and similar areas. Window-side lighting is controlled in the same manner as office areas, while the remaining areas use step-by-step dimming control (70%, 30%, 0%) when vacancy is detected by the occupancy sensor.
  • Scene control for executive offices and meeting rooms: PT Mode (50% Dimming), Meeting Mode (80% Dimming), and Energy-Saving Mode (30% Dimming).
  • Install occupancy sensors for individual LED luminaires in office areas and apply step-by-step dimming control when occupants are absent (70% after 30 minutes of vacancy, 30% after 60 minutes, and 0% after 120 minutes).
Energy Saving Analysis Table
Category ON/OFF System Dimming System DALI + Dimming System
Application
Area
Luminaire
Power (W)
Quantity
(EA)
Daily Operating
Hours
Operating
Days/Year
Annual Energy
Consumption (kWh)
Saving
Rate
Annual Energy
Consumption After Savings (kWh)
Saving
Rate
Annual Energy Consumption
After Savings (kWh)
Saving
Rate
Office 25 660 10 260 42,900 10% 38,610 10% 23,595 45%
Other Rooms 25 40 10 260 2,600 30% 1,820 35% 1,690 40%
Window-Side Area 10 120 10 260 3,120 30% 2,184 35% 2,028 35%
Restrooms & Other Rooms 10 60 10 260 1,560 5% 1,482 5% 1,482 5%
Total 880 50,180 43,810 28,665
Annual Electricity Cost (Based on KRW 145/kWh) 7,276,100 6,352,450 4,156,425
Annual Cost Savings 923,650 3,119,675
C O N D I T I O N S
  • Working hours are assumed to be 10 hours per day, consisting of 8 hours of focused work time and 2 hours of extended working hours.
  • Since the On/Off system does not support individual luminaire control, the circuits are divided into ZONES. The Dimming system is also designed to use ZONE-based circuit separation for dimming control rather than individual luminaire control.
  • For the DALI Dimming control system, individual lighting control is applied to offices, meeting rooms, and executive offices, while the window-side lighting is configured as ZONE-based circuits for dimming control.
  • Please refer to the energy-saving graphs on the following page for each applied system.
R E S U L T S
12,000 9,000 6,000 3,000 -
No System
ON/OFF Sys.
Dimming Sys.
DALI + Dimming Sys.
Annual Energy Consumption (kWh)
No System
ON/OFF Sys.
Dimming Sys.
DALI + Dimming Sys.