Application

Enhancing Building Value Through Optimized Solutions

화면 로딩 중...
DESIGN
Design Considerations and Key Design Factors
Application Areas Design Considerations
Operational Functionality
  • Office Areas
  • Meeting Rooms
  • Common Areas
  • Underground Parking
  • Define the targets and scope of lighting control
  • Determine the targets for ON/OFF or Dimming control
  • Select the appropriate dimming module type for office areas and underground parking (Office: DALI, Underground Parking: Wireless Dimming Module)
  • Select the appropriate illuminance sensor type (Indoor, Outdoor, Art Hall)
  • Select the appropriate occupancy sensor type (Unidirectional, Bidirectional, and detection range)
  • Select occupancy counter sensors or multisensors for restrooms
  • Determine the location and control range of programmable switches
  • Develop lighting ON/OFF and Dimming schedules according to time periods
  • Consider implementing sunset/sunrise functions
  • Integrate lighting control with the access control system
Energy Savings
  • Office Areas
  • Meeting Rooms
  • Common Areas
  • Underground Parking
  • Apply individual Dimming control to each LED luminaire or divide lighting into ZONES for ON/OFF control
  • Define the areas and equipment subject to time-based scheduling
  • Implement control functions using illuminance sensors and occupancy sensors
  • Apply Dimming control according to different meeting room Scenes
  • Apply standby power-saving and lighting control
  • Apply Dimming control to underground parking lighting using motion detection sensors (30% under normal conditions, 90–100% when motion is detected)
  • Apply ON/OFF control or 30–100% Dimming control to corridors and stairways (Sensor- or schedule-based control)
System Reliability
  • LED Lighting
  • Lighting Control Panels
  • Communication Devices
  • Central Monitoring System
  • Operating Software
  • Interfaces with Other Systems
  • Review the quantity of controlled devices: relay quantity and number of LED DALI Dimming Modules
  • Design using dedicated communication lines or the IBS backbone network
  • Define integration methods with other IBS systems
  • Determine whether a redundant system should be implemented
  • Compare and evaluate distributed control and centralized control architectures
  • Review communication data volume and transmission distances
  • Verify the availability of self-diagnostic functions and maintenance-related program operation